The supply that keeps the network up when the AC goes away.

DC systems

Industrial AC/DC rectifiers and chargers, lithium-ion and VRLA battery backup, modular UPS and smart energy management — sized, installed and maintained to IEEE standards.

When the incoming AC supply fails, the radios, transmission equipment, protection relays and SCADA gateways all run from one place: the DC plant and its battery. The rectifiers and chargers that keep it there are the least visible items in the room and the ones with the least tolerance for being wrong.

We supply, size, install and maintain DC power for central offices, tower shelters, substations and off-grid sites — industrial AC/DC chargers and rectifiers, lithium-ion and VRLA battery backup, modular UPS and smart energy management — against the standards your specification already references, and we issue the calculation rather than asking you to take the rating on trust.

  • Industrial AC/DC chargers and rectifiers

    High-efficiency power conversion units for central offices and tower shelters, with N+1 modular redundancy and hot-swappable rectifiers.

  • Battery backup and modular UPS

    Lithium-ion and VRLA power systems providing continuous operation during outages, with autonomy sized from your duty cycle to IEEE 485 rather than taken from a catalogue.

  • Smart energy management (EMS)

    Remote telemetry integration and hybrid solar/grid management for off-grid sites, so rectifier, battery, generator and fuel status are visible from the NOC.

  • Maintained before it fails

    Impedance or conductance testing trended against the commissioning values, so a cell degrading toward failure shows up on a report rather than during the next outage.

Capabilities

Scope of work

Design and sizing

Battery sizing
IEEE 485 for lead-acid, IEEE 1115 for nickel-cadmium, against your duty cycle
System architecture
Redundancy, distribution and protection coordination to IEEE 946 and IEEE 1375
Ambient derating
Rated against measured room temperature, with the derating curve issued
Ventilation
Hydrogen evolution assessment and ventilation requirements for the battery room

Typical ratings supplied

Nominal DC
24, 48, 110, 125 and 220 VDC
Output current
10 A to 600 A; higher by paralleled modules
Topology
Switchmode with N+1 redundant rectifiers, or SCR where specified
AC input
Three-phase or single-phase, matched to the site supply and frequency
Regulation
± 0.5 % no load to full load; ripple < 1 % RMS with the battery connected
Charge control
Float, boost/equalise and commissioning charge, temperature compensated at the battery
Battery chemistry
Lithium-ion and VRLA; nickel-cadmium where specified

Backup and energy management

Modular UPS
Modular, hot-swappable UPS for AC-critical loads
EMS telemetry
Remote monitoring of rectifiers, batteries, generators and fuel into the NOC
Hybrid power
Solar, grid and generator hybrid control for off-grid and weak-grid sites

Protection and monitoring

Earth-fault detection
Positive and negative bus, adjustable threshold, optional branch location
Alarms
AC fail, charger fail, DC over/under-voltage, earth fault, battery disconnected, fuse operated
Contacts
Individually wired potential-free changeover contacts
Protocols
Modbus RTU and TCP, DNP3, SNMP; IEC 61850 where the station is fully digital
Battery monitoring
Open-circuit detection, end-of-discharge alarm, optional cell-level monitoring

Installation and maintenance

Installation
Charger, distribution, battery stands or cabinets, interconnection and labelling
Commissioning
Full functional test, commissioning charge, cell voltage baseline recorded
Preventive maintenance
To IEEE 450, IEEE 1188 or IEEE 1106 by chemistry
Capacity testing
At the interval your insurer or regulator requires, with trended results
Replacement
Battery replacement programmes including removal of the old set

Figures on these pages describe what we routinely deliver. Anything specific to your site is confirmed from a survey before it is priced.

Standards we work to

  • IEEE 485

    Sizing lead-acid batteries for stationary applications

  • IEEE 1115

    Sizing nickel-cadmium batteries for stationary applications

  • IEEE 946

    DC auxiliary power systems for generating stations and substations

  • IEEE 1375

    Protection of stationary battery systems

  • IEEE 450 / 1188 / 1106

    Maintenance and testing — vented lead-acid, VRLA and nickel-cadmium

  • IEC 61439-1/-2

    Low-voltage switchgear and controlgear assemblies

  • UL 1012

    Power units other than Class 2

  • NFPA 70 Art. 480

    Storage batteries — installation requirements

  • IEEE 1679.1

    Lithium-based batteries in stationary applications

  • UL 9540

    Energy storage systems and equipment

Typical applications

  • Telecom central offices and tower shelters
  • Off-grid and hybrid solar/grid sites
  • Substation protection and control — trip, close and relay supply
  • Switchgear spring-charging motors and motorised isolators
  • SCADA gateways, RTUs and IEDs
  • Telecom equipment rooms at −48 VDC and +24 VDC
  • Fire and gas detection and emergency shutdown panels
  • Generating plant and turbine control systems
  • Emergency lighting inverter DC input

What you receive

  • IEEE 485 or IEEE 1115 sizing calculation for your duty cycle
  • General arrangement drawing, schematic and terminal schedule
  • Alarm and communications point list, issued before manufacture
  • Factory and site acceptance test records, countersigned
  • Commissioning charge record with individual cell or block voltages
  • Operation and maintenance documentation and operator training
  • Recommended two-year spares holding, priced at order stage

Where we do it

  • Power & utilities

    Protection, control, SCADA communications and DC power for grids and substations.

  • Oil & gas

    Hazardous-area communications and DC power for plants, terminals and offshore.

  • Transportation

    Operational radio, corridor networks and passenger communications for transport.

Frequently asked questions

Before you send an enquiry

Switchmode or SCR?

Switchmode is the default for new work: modular N+1 redundancy, hot-swappable rectifiers, high power factor and a much smaller footprint. SCR remains appropriate where the specification mandates it, where an existing fleet needs to stay consistent, or where the bus feeds unusually noisy inductive loads. If your specification is silent, we propose switchmode and explain the trade-off.

Can you work on an existing installation?

Yes — extensions, like-for-like replacements and battery changes are routine. Send the nameplate of the existing unit, the battery details and a photograph of the DC distribution section. Matching the alarm contact arrangement usually matters more than matching the physical dimensions.

How often should the battery be capacity tested?

IEEE 450 suggests an acceptance test, a performance test within the first two years, and then periodically at intervals that shorten as the battery ages — with annual impedance trending in between. The right interval for your site also depends on criticality and what your insurer expects, and we will recommend one rather than default to the longest permissible.